100KW Cummins Diesel Generator PL-C100GF

Cummins Series Diesel Generator

  • Description
  • Inquiry

Genset technical data

ModelPL-C100GF
Prime Power 92KW
Standby Power100KW
PhaseAC Three Phase
Rated Voltage220/380, 230/400V
Prime Current175A
Frequency50Hz
P.F (COS¢)0.8
Noise Level68-71 dB(A) at 7 meters
Weight1680 kg
Dimension280*105*160 cm

Prime power

This rating is for the supply of continuous electrical power (at variable load). There is no limit on the annual hours of operation and 10% overload power can be supplied for 1 hour in 12.

Standby power

This rating is for the supply of continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted.

 General features:

  • Every generator set is subjected to a comprehensivetest program which includes 50% load, 75% load,100% load, 110% load and the checking and proving of all control and safety shut-down functions;
  • 24V DC start motor;
  • Equipped 24V highperformance maintenance-free lead-acid starting batteries and connecting with cables;
  • Equipped with industrial silencer and flexible exhaust hose;
  • Designed to Comply with ISO8528/GB2820;

Powered by Cummins engine, KAIJIELI alternator and Smartgen control panel.

Cummins engine technical data

Engine Model6BTA5.9-G2
Number of Cylinders6 cylinders in line
Cycle4 stroke
AspirationTurbocharger
Bore×Stroke 102mm x 120mm
Displacement5.9L
Compression ratio17.3:1
Prime Power/Speed106kw /1500rpm
Standby Power/Speed116kw /1500rpm
Speed GovernorElectrical
Cooling SystemForced water cooling cycle
Steady speed droop≤1%
Total lubrication system capacity(High – Low)14.2-12.3L
Coolant capacity (engine only)10L
Fuel Consumption at 75% Load23 L/hr (at 1500 rpm)
Fuel Consumption at 100% Load31 L/hr (at 1500 rpm)
Starter Motor and AlternatorDC24V

KAIJIELI alternator technical data

Alternator ModelTWGII274C
Rated voltage220/380V, 230/400V
Standby power105KW
Frequency/speed50Hz/1500rpm
Exciter typeSingle bearing, Brushless, Self-excited
Voltage regulator typeAVR
Power factor0.8
Voltage adjust range≥5%
Voltage regulation NL-FL≤±1%
Insulation GradeH
Protection GradeIP23
Phase3 Phases 4 Wires

Smartgen control panel data

ModelHGM6120
The control module gives digital readouts of:

Generator voltage;

Output frequency;

Engine speed;

Battery voltage;

Engine hours run.

The control module has indicators for failure

information:

Overspeed/underspeed,

Emergency stop

Low oil pressure;

High water temperature

Failure to start

Battery charger failure

Automatic shutdown occurs under:

Low engine oil pressure;

High engine water temperature;

Overspeed/underspeed;

Failure to start after three attempts.

Standard accessories

Standard AccessoriesOpen typeSilent type
Sound-proof & Weather-proof CanopyN/A
Daily base fuel tank. 8 hours capacityN/A
Single-bearing generator again drops
Intelligent LED display control panel
Speed governor
Electric start and 24v charger
Standard air filter, oil filter, fuel filter
Cooling water tank
High-efficient silencer.
Exhaust elbow
Storage battery
Steel base-frame against vibration
Soft pipe for fuel and handle for lube going-out
Operation& Maintenance manual.

Contact Us